Terminal Blocks for Factory or Field Wiring.  How to know what you’re getting –

 

Terminal Blocks come in many different forms.  They’re rated for difference wire sizes, voltages and ampacities, temperatures, short circuit ratings, and more.

 

Many don’t know, however, UL also rates them for Factory or Field wiring.  Terminal Blocks rated for Factory wiring only, cannot be used for wires to be installed in the field.  So, if you’re at UL with your product that has a Terminal Block intended to be wired in the field, you better make sure you pick the right one.

 

Picking the right one –

 

UL designates Terminal Blocks for Factory or Field Wiring.  See below from UL’s Guide Card on Terminal Blocks -

 

XCFR2.GuideInfo - Terminal Blocks - Component

 

Factory and/or Field Wiring (FW) — These terminal blocks are rated for: Code 1, factory wiring only, or Code 2, both factory and field wiring. The suitability of the connections (including spacings between factory connectors) shall be determined in the end-use application.

Unless noted with a "CA 4" in the last column, a terminal connector suitable for field wiring has been investigated to ANSI/UL 486A-486B, "Wire Connectors."

When Code 1 and Code 2 terminals are intermixed on the same terminal block, both codes will be used with suitable indication for which terminal each code applies, i.e., 1/2.

 

 

 

When looking for the right Terminal Block, look in the FW column on the companies UL Recognition card.

 

 

 

Series
No.

Wire
Range

Wire
Type


FW

TQ
In.-Lb


V


A


UG


CA

+FP

14

Cu

1

300

20

C

2(130),#

+FS

14

Cu

1

300

20

C

2(130),#

@FP-XX-25A

12

Cu

1

300

25

C

2(130),#

@FS-XX-25A

12

Cu

1

300

25

C

2(130),#

+D exept for D-11

4-18 SOL/STR

Cu

2

20

250/300

85

B/C

2(130),#

 

(2) 12-16 STR

Cu

2

20

250/300

35

B/C

2(130),#

 

(2) 18 SOL/STR

Cu

2

20

250/300

     
 

 

An established fountain manufacturer came to us at a previous Lightfair inquiring about their first underwater LED lighting project. LED technology was new to them and presented many unique challenges for their lighting systems. To make matters worse, they were operating under a tight schedule.

 

Product Safety Consulting was able to quickly help them using our Design For Safety Approval™ process. This process includes a variety of services outlined below.

  • Design Review – From drawings, we can conduct an initial review confirming the required Standard(s), confirming requirements that pertain to your product, providing recommendations on possible non-compliances, getting your design team headed in the right direction.
  • Construction Evaluation – We go through the Standard, paragraph by paragraph, confirming compliance. If non-compliances are found, we provide recommendations on how to bring the product into compliance.
  • Testing – We conduct the testing and confirm compliance. Again, if non-compliances are found, we provide recommendations on how to bring the product into compliance.
  • Submittal Management – We submit on your behalf and manage the product until Certification is issued.

Product Safety Consulting has been helping companies obtain UL, CSA, ETL and CE approvals for more than 26 years.  John Allen, our President and Founder, will be available to provide his compliance expertise and to help answer your technical questions.  We highly recommend setting up an appointment either at our booth or yours so we can set time aside for you.